MMC AND MMC FOR PC HARDWARE
This PDF document is a subset of the Sheffield Automation MMC Controls, Block I/O and Cimrex HMI Product Guide, P/N M.1301.6219.
NOTE
Progress is an ongoing commitment at Sheffield Automation. We continually strive to offer the most advanced products in the industry; therefore, information in this document is subject to change without notice. The illustrations and specifications are not binding in detail. Sheffield Automation shall not be liable for any technical or editorial omissions occurring in this document, nor for any consequential or incidental damages resulting from the use of this document.
DO NOT ATTEMPT to use any Sheffield Automation product until the use of such product is completely understood. It is the responsibility of the user to make certain proper operation practices are understood. Sheffield Automation products should be used only by qualified personnel and for the express purpose for which said products were designed.
Should information not covered in this document be required, contact the Customer Service Department, Sheffield Automation, 660 South Military Road, P.O. Box 1658, Fond du Lac, WI 54936-1658. Sheffield Automation can be reached by telephone at 920 921 7100.
Version 2.0
Copyright © 1999 - 2003 Sheffield Automation, LLC
Belden is a trademark of Cooper Industries, Inc.Cimplicity is a trademark of GE FanucAutomation North America, Inc.Cimrex is a trademark of Cimrex Electronic ABData Highway Plus is a trademark of Allen-Bradley CompanyDeviceNet is a trademark of Iris Technologies, Inc.IEEE is a trademark of the Institute of Electrical and Electronics EngineersIntellution is a trademark of Intellution, Inc.Modbus is a trademark of Gould, Inc.Modicon is a trademark of Modicon CorporationNEMA is a trademark of the National Energy Manufacturers AssociationOPC OLE for Process Control is a trademark of OPC FoundationPentium is a trademark of Intel CorporationRSView is a trademark of Rockwell Software, Inc.Windows NT, Windows 2000 Windows XP, MS-DOS, QuickBASIC, and Microsoft are trademarks of Microsoft CorporationWonderware is a trademark of Wonderware CorporationPiC900, PiC90, PiCPro, PiCServoPro, PiCMicroTerm, Centurion, and MMC are trademarks of Giddings & Lewis, LLC
Table of Contents: MMC and MMC for PC Hardware
MMC (Machine and Motion Control) ................................................................ 37MMC (Machine and Motion Control) .......................................................... 39MMC Mounting Instructions ........................................................................ 46MMC Accessories ......................................................................................... 47
MMC Breakout Box ............................................................................... 47 MMC Breakout Box Cables ................................................................... 49 MMC Flying Lead Cables ...................................................................... 49
MMC Specification Table .......................................................................... 51MMC Axis I/O Option Module .................................................................... 56MMC Ethernet - TCP/IP Module .................................................................. 58MMC DeviceNet Module ............................................................................. 61
Introduction............................................................................................. 61 Connections ............................................................................................ 62 The DeviceNet Port ................................................................................ 63 The Configuration (RS232) Port............................................................. 63 LEDs ....................................................................................................... 64 Theory of Operation................................................................................ 65 Specifications.......................................................................................... 66
MMC Profibus Module ................................................................................. 67 Introduction............................................................................................. 67 Connections ............................................................................................ 68 The Profibus Port .................................................................................... 69 The Configuration (RS232) Port............................................................. 69 LEDs ....................................................................................................... 70 Theory of Operation................................................................................ 71
MMC for PC (PC Machine and Motion Control) ............................................... 73MMC for PC (PC Machine and Motion Control) ......................................... 74
MMC for PC ........................................................................................... 77 Analog Servo Interface Unit (ASIU) ...................................................... 79 Optional Fieldbus Modules..................................................................... 87 Specification Tables................................................................................ 94
MMC CONTROLS, BLOCK I/O AND CIMREX HMIMOTION SOLUTIONS PRODUCT GUIDE
MMC (Machine and Motion Control)
Sheffield Automation
MMC (Machine and Motion Control)
MMC (Machine and Motion Control)
MMC family controls include the analog-interfaced MMC-A2 (2-1/2 axis) and MMC-A4 (4-1/2 axis), the MMC-A2 Plus (2-1/2 axis expandable to 18), and MMC-A4 Plus (4-1/2 axis, expandable to 20), and the SERCOS-interfaced MMC-S8 (8 axis) system.
Description. The MMC (Machine and Motion Control) is a compact, full-featured total machine control solution for applications requiring one to twenty axes of servo motion con-trol. All three versions have the same compact footprint (9 inches tall, 2.125 inches wide and 5.25 inches deep).
Programming. The MMC is programmed using IEC61131 ladder logic, function blocks, and structured text. The same programming software, PiCPro for Windows, is used across the entire family of PiC and MMC products.
Features. Some of the powerful features that are available in PiCPro for Windows are ani-mation, variable force and view, cam profiles, linear and circular interpolation, registration, multi-tasking, and UDFBs. With virtually no re-programming, an application can be loaded into an MMC, PiC90, or PiC900 control. This allows you to expand your motion control sys-tem from one product to another without wasting valuable engineering time.
Expanded Features. The MMC offers features and flexibility far beyond a typical motion controller, including total machine control capability, a single programming language for logic and motion, on-line edit of the motion program, Ethernet TCP/IP networking capability, distributed block I/O expansion, PLS outputs, and close-coupled logic and motion. The MMC is priced to be competitive with motion controllers, while offering a flexible, powerful total machine control solution instead of motion only.
Expandability. The MMC is expandable by using the Ethernet TCP/IP and/or Fieldbus (DeviceNet or Profibus) field-installable expansion modules. The Ethernet TCP/IP expan-
Sheffield Automation MMC Controls, Block I/O and Cimrex HMI Motion Solutions Product Guide 39
MMC (Machine and Motion Control)
sion module can be used for distributed control as well as remote troubleshooting over the Internet. The Fieldbus module is a master or scanner module that is used to scan the I/O on a DeviceNet or Profibus network.
Quick Start Example Programs. Included with PiCPro for Windows are several applica-tion example programs for the MMC to get you started in a matter of minutes. You can build off of these applications and customize them for your machine.
Processor. The MMC processor provides 256K of application memory and 128K of RAM-DISK memory. The processor has floating point capability. There is 2 Megabytes of flash memory resident on the CPU to store the source code for your application using the Project Manager. The system firmware is also stored in flash memory and is software-loadable.
Axis A1 to A4 Connectors. On the analog MMC, each axis connector (labeled A1 to A4) provides a connection to a servo amplifier. Each axis connector contains a differential encoder input, a +/- 10V analog output, two 24VDC discrete outputs for drive enable and drive reset, and one 24VDC discrete input for the drive ready or drive OK signal. Only one cable is required to interface an MMC to MMC Smart Drive amplifier. Encoder inputs and analog outputs not used for closed loop servos can be used for variable frequency drives or additional master axes.
Aux I/O. On the analog MMC, the Aux I/O connector contains the fast inputs for each axis (including the half axis encoder input) for registration and hardware interrupt capability. It also contains the differential encoder input for the half axis, one analog input, and three 24VDC discrete inputs for each closed loop axis. Typically these inputs would be used for plus and minus end of travel limits and for the reference switch. However, they can be used as general purpose inputs if they are not being used for end-of-travel and reference switch.
Input Power. The MMC input power is a 24V screw terminal connection.
Gen I/O. The Gen I/O connector contains sixteen general-purpose 24 VDC discrete inputs (sink or source) and sixteen general-purpose 24 VDC discrete outputs (source only). Any of the 16 outputs can be used as CAM or PLS outputs. Two of the inputs (number 1 and number 9) have hardware interrupt capability and can be used to trigger hardware interrupt tasks in the application program.
User Port. The user port connector is a serial port typically used for a Cimrex operator inter-face. This port has multi-drop capability (RS232, RS422, or RS485) and can run at baud rates up to 19.2K baud.
Block I/O. The Block I/O connector is used for communicating with distributed block I/O modules. Up to 77 blocks can be connected to a single MMC. A complete family of block I/O modules are available, including AC and DC discrete I/O, analog I/O, stepper and resolver.
PiCPro Connector. The PiCPro connector is used for communicating with a PC when run-ning PiCPro for Windows.
Cables. There are a number of plug and play cables available to facilitate MMC field wiring. Three connector types of cables can be used with the A1 to A4 connectors, including an MMC Smart Drive, a flying lead connector, or a breakout box connector. For the AUX I/O, GEN I/O, USER PORT, and BLOCK I/O connectors, there are two types of cables that can be used: A breakout box connector or a flying lead connector. For the PiCPro connector, the standard PiCPro cable is used.
40 MMC Controls, Block I/O and Cimrex HMI Motion Solutions Product Guide Sheffield Automation
MMC (Machine and Motion Control)
PiCPro Port
Block I/O
User Port
General I/O
Power
Axis 4 Port
Axis 3 Port
Axis 2 Port
Axis 1 Port
Auxiliary
LEDs
I/O Port
Port
Port
Connection
AUX I/O Connector
Flying Lead
to Flying Lead
AUX I/O to
To Breakout Box
Breakou Box Cable
AUX I/OBreakout Box
MMC Block I/O
To Flying Leads
to Flying Lead
Choose 1
Choose 1 per Axis
Choose 1
MMC Block I/O to
To Breakout Box
Breakout Box Cable
MMC Block I/OBreakout Box
OR
OR
GEN I/O to
To Flying Lead
Flying Lead
Choose 1
GEN I/O to
To Breakout Box
Breakout Box Cable
GEN I/OBreakout Box
OR
User Port to
To Flying Lead
Flying Lead
Choose 1
User Port to
To Breakout Box
Breakoutbox Cable
User PortBreakout Box
OR
Connection Selector Sheetfor MMC Analog Control
MMC-A4 4 Axis Analog MMC shown(MMC-A2 2 Axis Analog MMC also available)
Flying Lead
MMC Axis toFlying Lead
To Breakout Box
MMC Axis toBreakout Box Cable
MMC AxisBreakout Box
MMC Smart Drive
MMC Axis toDrive I/O
Sheffield Automation MMC Controls, Block I/O and Cimrex HMI Motion Solutions Product Guide 41
MMC (Machine and Motion Control)
PiCPro
Block I/O
User
General I/O
Power
LEDs
Port
Port
Port
Connection
Port
RECV
XMIT
LOADER
MMC Block I/O
To Flying Leads
to Flying Lead
Choose 1
MMC Block I/O to
To Breakout Box
Breakoutbox Cable
MMC Block I/O Breakout Box
OR
Connection Selector Sheetfor MMC SERCOS Control
MMC-S8 8 Axis
User Port to
To Flying Leads
Flying Lead
Choose 1
User Port to
To Breakout Box
Breakoutbox Cable
User PortBreakout Box
OR
SERCOS MMC Control GEN I/O to
To Flying Leads
Flying Lead
Choose 1
GEN I/O to
To Breakout Box
Breakoutbox Cable
GEN I/OBreakout Box
OR
42 MMC Controls, Block I/O and Cimrex HMI Motion Solutions Product Guide Sheffield Automation
MMC (Machine and Motion Control)
MMC Machine and Motion Controls - Part Numbers
MMC Machine and Motion Controls Connectors - Part Numbers
MMC Machine & Motion Controls
Description Part Number
MMC-A2 2 Axis Analog MMC M.1017.3772
MMC-A2 Plus (expandable) M.1302.7095
MMC-A4 4 Axis Analog MMC M.1017.3774
MMC-A4 Plus (expandable) M.1302.7096
MMC-S8 8 Axis SERCOS MMC M.1017.3770
MMC Axis Connector Cables and Breakout Box(only for MMC Servo Control Axis Ports A1, A2, A3, A4)
MMC Smart Drive
Description Length Part Number
MMC Axis A ‘n’ to Drive IO Connector0.5 meters M.1302.5990
1 meter M.1302.5991
1.5 meters M.1302.5992
3 meters M.1302.5993
Flying Lead
Description Length Part Number
MMC Axis A’n’ to Flying Lead Cable 10’ M.1016.2519
Breakout Box
Description Length Part Number
MMC Axis A’n’ to Breakout Box Cable1’ M.1016.2535
2’ M.1016.2536
3’ M.1016.2537
MMC Connector Breakout Box N/A M.1016.2529
Sheffield Automation MMC Controls, Block I/O and Cimrex HMI Motion Solutions Product Guide 43
MMC (Machine and Motion Control)
MMC Auxiliary I/O Connector Cables and Breakout Box
Flying Lead
Description Length Part Number
MMC Aux I/O Connector to Flying Lead 10’ M.1016.2566
Breakout Box
Description Length Part Number
MMC Gen/Aux I/O Connector to Breakout Box Cable
1’ M.1016.2539
2’ M.1016.2540
3’ M.1016.2541
MMC Aux I/O Breakout Box N/A M.1016.2531
MMC Connector Breakout Box with Encoder Isolation
N/A M.1016.4236
MMC Block I/O Connector Cables and Breakout Box
Flying Lead
Description Length Part Number
MMC Block I/O Connector to Flying Lead 10’ M.1016.2568
Breakout Box
Description Length Part Number
MMC Block I/O Connector to Breakout Box Cable
1’ M.1016.2543
2’ M.1016.2544
3’ M.1016.2541
MMC Block I/O Breakout Box N/A M.1016.2533
44 MMC Controls, Block I/O and Cimrex HMI Motion Solutions Product Guide Sheffield Automation
MMC (Machine and Motion Control)
MMC User Port I/O Connector Cables and Breakout Box
Flying Lead
Description Length Part Number
MMC User Port to Flying Lead 10’ M.1016.2565
Breakout Box
Description Length Part Number
MMC User Port to Breakout Box Cable1’ M.1016.2715
2’ M.1016.2716
3’ M.1016.2717
MMC User Port Breakout Box N/A M.1016.2530
MMC General I/O Connector Cables and Breakout Box
Flying Lead
Description Length Part Number
MMC Gen I/O Connector to Flying Lead 10’ M.1016.2567
Breakout Box
Description Length Part Number
MMC Gen/Aux I/O Connector to Breakout Box Cable
1’ M.1016.2539
2’ M.1016.2540
3’ M.1016.2541
MMC Gen I/O Breakout Box N/A M.1016.2532
Sheffield Automation MMC Controls, Block I/O and Cimrex HMI Motion Solutions Product Guide 45
MMC Mounting Instructions
MMC Mounting Instructions
Mount the unit to your cabinet using the mounting slots on the MMC. The MMC unit may be mounted vertically or horizontally. The recommended size of mounting hardware is #10 bolts with #10 star washers (to ensure proper ground connection). MMC-A2 and MMC-A4 controls can have up to twooption modules. MMC-A2 Plus and MMC-A4 Plus controls can have up to four option modules.
MMC Mounting Dimensions
46 MMC Controls, Block I/O and Cimrex HMI Motion Solutions Product Guide Sheffield Automation
MMC Accessories
MMC Accessories
MMC Breakout BoxThere are five MMC Breakout Boxes available that simplify wire termination to the MMC Controls.
Breakout Box Dimensions
Dimensions - 44-Pin Breakout Box for AUX I/O and GEN I/O MMC Connectors
Breakout Box Description Part Number
MMC Axis Connector Breakout Box M.1016.2529 MMC Auxiliary I/O Breakout Box M.1016.2531 MMC User Port Breakout Box M.1016.2530 MMC General I/O Breakout Box M.1016.2532 MMC Block I/O Breakout Box M.1016.2533
1.875”
2.625”
3.940”
1 22
23 44
5.312”
Sheffield Automation MMC Controls, Block I/O and Cimrex HMI Motion Solutions Product Guide 47
MMC Accessories
Dimensions - 15-Pin Breakout Box for Axis and User Port MMC Connectors
Dimensions - 9-Pin Breakout Box for Block I/O MMC Connector
1.750”
2.250”
3.000”
1
9
2.250”
8
15
1.750”
2.250”
3.000”
1
6
1.750”
5
9
48 MMC Controls, Block I/O and Cimrex HMI Motion Solutions Product Guide Sheffield Automation
MMC Accessories
MMC Breakout Box Cables
MMC Flying Lead Cables
Breakout Box Cable Description Length Part Number
MMC Axis A’n’ to Breakout Box Cable
1’ M.1016.2535 2’ M.1016.2536 3’ M.1016.2537
MMC User Port to Breakout Box Cable
1’ M.1016.2715 2’ M.1016.2716 3’ M.1016.2717
MMC Gen/Aux I/O Connector to Brea-kout Box Cable
1’ M.1016.2539 2’ M.1016.2540 3’ M.1016.2541
MMC Block I/O Connector to Brea-kout Box Cable
1’ M.1016.2543 2’ M.1016.2544 3’ M.1016.2545
Flying Lead Cable Description Length Part Number
Flying Lead Cable to MMC Axis A’n’
10 ‘ M.1016.2519
Flying Lead Cable to MMC User Port
10’ M.1016.2565
Flying Lead Cable to MMC General I/O Connector
10’ M.1016.2567
Flying Lead Cable to MMC Auxiliary I/O Connector
10’ M.1016.2566
Flying Lead Cable to MMC Block I/OConnector
10’ M.1016.2568
Sheffield Automation MMC Controls, Block I/O and Cimrex HMI Motion Solutions Product Guide 49
MMC Accessories
50 MMC Controls, Block I/O and Cimrex HMI Motion Solutions Product Guide Sheffield Automation
MMC Specification Table
MMC Specification Table
*The number of axes that can be run at a particular update rate depends on the use of available memory and CPU execution time. Examples of software that are heavy users of these resources include servo tasks, S-curve, RATIO_RL, M_LINCIR, M_SCRVLC, PLS, and CAM_OUT. Consult Sheffield Automation for assis-tance if you want to exceed the number of axes in this chart.
GeneralCharacteristic MMC Specifications
Number of servo axes availableat six update rates*
Model Part Number SpeedApp Mem
RAM Mem
User Mem 8 ms 4 ms 2 ms 1 ms .5 ms
.25 ms
MMC-A2 M.1017.3772 Std. 256K 128K 64K 2 2 2 2 2 1
MMC-A2 Plus
M.1302.7095 X3 256K 128K 64K 18 18 16 8 3 1
MMC-A4 M.1017.3774 Std. 256K 128K 64K 4 4 4 4 2 1
MMC-A4 Plus
M.1302.7096 X3 256K 128K 64K 20 20 16 8 3 1
MMC-S8 M.1017.3770 Std. 256K 128K 64k 8 8 8 4 n/a n/a
CPU 32 bit RISC processor with numeric coprocessor
Battery 3V Coin Cell, BR2032 lithium battery
CAUTION for Lithium BatteriesDanger of explosion if battery is incorrectly replaced. Replace only with the same or equivalent type recommended by the manufacturer. Dispose of used batterries according to the manufac-turer’s instructions.
Flash Disk 2 Megabytes
Memory 1 Megabyte max.
PiCPro Port (to workstation) RS232 serial port, secured protocolSoftware selectable baud rate to 57.6K
User Port (to serial interface device) RS232/RS485 serial portSupports RTS/CTS hardware handshakingSoftware selectable baud rate to 19.2K
Input voltage 20 VDC to 30 VDC
Input power 250 mA plus I/O power
Time-of-day clock
Clock tolerance
Access via PiCPro 10.2 and above or your application programAt 25°C (77°F),±1 second per dayOver temperature, voltage and aging variation,2-1/2 seconds per day
Sheffield Automation MMC Controls, Block I/O and Cimrex HMI Motion Solutions Product Guide 51
MMC Specification Table
Operating temperature range 5°C to 55°C (41°F to 131°F)
Storage temperature range -40°C to 85°C (-40°F to 185°F)
Humidity 5 to 95%, non-condensing
CE Marked Conforms to Directives 73/23/EEC, 89/336/EEC, 92/31/EEC, 93/68/EEC by conforming to the following standards:EN 50081-2:1993EMC Generic Industrial EmissionsEN 50082-2:1995EMC Generic Industrial ImmunityEN 61131-2:1994/A11:1996 Low voltage directive requirements for programmable controllersOperates with emissions below EN55011/ CISPR 11Class A limitsImmune to:•Electrostatic discharge (4K V contact mode, 8K V air discharge) per EN61000-4-2•RF electromagnetic fields per EN61000-4-3, ENV 50141, and ENV50204•Electrical fast transients per EN61000-4-4 •Magnetic fields per EN61000-4-8Refer to the EMC Guidelines for more information.
UL and C/UL Listed E126417
Physical size 2.25" wide x 9.6" high x 5.3" deep 57.15 mm x 243.84 mm x 134.62 mm
Analog Output
Output channels 2 or 4
Resolution 16 bits
Output voltage range ±10 VDC
Maximum output current (1K ¾ load)
±10 mA
Power on output voltage 0 V ±100 mV
Scan loss output voltage 0V ±100 mV
Accuracy ±0.375% of FSR Drift ± 50ppm/°C
Update rate 68 µsec
52 MMC Controls, Block I/O and Cimrex HMI Motion Solutions Product Guide Sheffield Automation
MMC Specification Table
Analog Input
Input channel 1
Resolution 12 bits
Input voltage range ±10 V
Accuracy ±0.2% of FSR
Sample rate 100 µsec
Common mode filter 3 dB @ 10 K Hz
Differential mode filter 3 dB @ 475 Hz
Encoder Input
Input channels 3 or 5
Input receiver type 2632 differential RS422 type receiver
Encoder signals Differential quadrature
Input threshold ±200 mV
Input termination 120 ¾
Maximum input voltage 5 V
Maximum A or B input frequency 250 K Hz (1 M feedback unit count rate)
Fast input voltage Nominal 24 VDC, maximum 30 VDC
Guaranteed on voltage 15 VDC
Guaranteed off voltage 5 VDC
Turn on/off time 1 ms
Sheffield Automation MMC Controls, Block I/O and Cimrex HMI Motion Solutions Product Guide 53
MMC Specification Table
General, Auxiliary and Axis DC Inputs
Configuration There are 16 general inputs. The auxiliary inputs are divided into two groups of six inputs. Each group can be configured for sourcing or sinking. The axis inputs have one input per axis. Each input can be configured for sourcing or sinking.Operates with IEC Type 1 inputs (per IEC 1131=2).
Input voltage Nominal 24 VDC, maximum 30 VDC
Guaranteed on voltage 15 VDC
Guaranteed off voltage 5 VDC
Turn on/off time 1 ms
General DC Outputs
Number of outputs 16 outputs
Input voltage Nominal 24 VDC, 30 VDC maximum
Configuration Two groups of eight solid-state switches.
Protection of logic circuits Optical isolation between the logic and field side, transient suppression on the 24V external supply
Maximum current .25 A per output
Voltage range 24 VDC nominal, 5 to 30 VDC
Switch characteristics Solid-state switches
Time delay on for resistive loads 50 µsec max
Time delay off for resistive loads 50 µsec max
Leakage current in off state 0.5 mA max
Switch voltage, maximum ON 1 VDC max
Short circuit protection for each group
15 A (max) pulses for about 130 µsec every 100 msec until short is removed
Scan loss response Outputs turn off
54 MMC Controls, Block I/O and Cimrex HMI Motion Solutions Product Guide Sheffield Automation
MMC Specification Table
Axis DC Outputs
Number of outputs 2 outputs per axis
Configuration Each set of axis outputs can be configured as sourcing or sinking.
Maximum current 100 mA per output
Voltage range 24 VDC nominal, 5 to 30 VDC range
Scan loss responese Outputs turn off
Available I/O
I/OMMC-A2
2 1/2 AxisMMC-A4
4 1/2 Axis
MMC-S8 8-Axis
SERCOSAnalog Inputs 1 1 0
Analog Outputs 2 4 0
Encoder Inputs 3 5 0
Axis DC Inputs 2 4 0
Axis DC Outputs 4 8 0
Axis Fast DC Inputs 3 5 0
AUX I/O Port DC Inputs 6 12 16
General I/O Port DC Inputs 16 16 16
General I/O Port DC Inputs 16 16 16
Sheffield Automation MMC Controls, Block I/O and Cimrex HMI Motion Solutions Product Guide 55
MMC Axis I/O Option Module
MMC Axis I/O Option Module
The Axis I/O Option Module is used with the MMC-A2 Plus or MMC-A4 Plus control to provide control of up to four additional servo amplifiers. PiCPro for Windows Profes-sional Edition is required to program MMC Plus applications using the axis I/O Option Module.
Axis A1 to A4 Connectors. On the Axis I/O Option Module, each axis connector (labeled A1 to A4) provides a connection to a servo amplifier. Each axis connector con-tains a differential encoder input, a +/- 10V analog output, two 24VDC discrete outputs
MMC Axis I/O Option Module
56 MMC Controls, Block I/O and Cimrex HMI Motion Solutions Product Guide Sheffield Automation
MMC Axis I/O Option Module
for drive enable and drive reset, and one 24VDC discrete input for the drive ready or drive OK signal. Only one cable is required to interface an MMC to MMC Smart Drive ampli-fier. Encoder inputs and analog outputs not used for the closed loop servos can be used for variable frequency drives or additional master axes.
Aux I/O. On the Axis I/O Option Module, the Aux I/O connector contains the fast inputs for each axis (including the half axis encoder input) for registration and hardware interrupt capability. It also contains the differential encoder input for the half axis, one analog input, and three 24VDC discrete inputs for each closed loop axis. Typically, these inputs would be used for plus and minus end of travel limits and for the reference switch. How-ever, they can be used as general purpose inputs if they are not being used for end-of-travel and reference switch. Refer to the MMC Specification Table Analog Output, Encoder Input, and General, Auxiliary and Axis DC Inputs specifications for detailed information.
AVAILABLE I/O
I/O MMC-AIO
Analog Inputs 1
Analog Outputs 4
Encoder Inputs 5
Axis DC Inputs 4
Axis DC Outputs 8
Axis Fast DC Inputs 5
AUX I/O Port DC Inputs 12
Sheffield Automation MMC Controls, Block I/O and Cimrex HMI Motion Solutions Product Guide 57
MMC Ethernet - TCP/IP Module
MMC Ethernet - TCP/IP Module
The ETHERNET - TCP/IP module provides the MMC with Ethernet access and Internet connectivity. A 10Base T connection is provided following the IEEE 802.3 specification. The data transfer rate is 10 Mbps. Applications can range from connecting several MMCs, connecting groups of MMCs and PCs, or connecting to a system that includes Internet access. At the end of this document is a partial list of Internet links to useful information about Ethernet and TCP/IP networking.
The Remote Programmer Access switch will allow you to enable/disable PiCPro for Win-dows running over Ethernet. The DIAG LED goes on briefly while the diagnostic tests are running shortly after power is applied.
RS232 COM Port 2
RS232 COM Port 1
10 Base TRJ-45 8-pin connector
Remote Programmer Access Switch
RS232 COM Ports
Ethernet Port LEDs
Diagnostic LED
COM2
10 BaseT
REMOTEPROGRAMMER
ACCESS
Disable
Enable
COM2
COM1
OUT IN
OUT IN
COL PREV
GDLNK EO EI
ETHERNET
COM1
MMC Ethernet - TCP/IP Module
58 MMC Controls, Block I/O and Cimrex HMI Motion Solutions Product Guide Sheffield Automation
MMC Ethernet - TCP/IP Module
Specification Table
Characteristics Ethernet - TCP/IP Module Specifications
Function Provides Ethernet access and Internet connectivity
Part Number M.1017.3888
RS232 Port 1 Com Port 1 modem (future)
RS232 Port 2 Com Port 2 (for firmware and configuration loading)
10Base T RJ-45 8-pin connector Maximum twisted pair length is 100 m (328 ft.).
24 VDC Power from the MMC 200 mA
Operating temperature range 7° C to 55° C (45° F to 131° F)
Storage temperature range -40° C to 85° C (-40° F to 185° F)
Humidity 5 to 95%, non-condensing
CE Marked Conforms to Directives 73/23/EEC, 89/336/EEC, 92/31/EEC, 93/68/EEC by conforming to the following stan-dards:EN 50081-2:1993 EMC Generic Industrial EmissionsEN 50082-2:1995 EMC Generic Industrial ImmunityEN 61131-2:1994/A11:1996 Low voltage directive requirements for programmable controllersOperates with emissions below EN55011/ CISPR 11Class A limitsImmune to:• Electrostatic discharge (4K V contact mode, 8K V air discharge) per EN61000-4-2• RF electromagnetic fields per EN61000-4-3, ENV 50141, and ENV50204• Electrical fast transients per EN61000-4-4 • Magnetic fields per EN61000-4-8Refer to the EMC Guidelines for more information.
UL and C/UL Listed E126417
Physical size 1.3" wide x 9.6" high x 5.3" deep33 mm x 244 mm x 135 mm
Vibration (per IEC 68-2-6) 10-57 Hz (constant amplitude .15 mm)57 - 2000 Hz (acceleration 2 g)
Shock (per IEC 68-2-27) Four shocks per axis (15g/11 msec)
Sheffield Automation MMC Controls, Block I/O and Cimrex HMI Motion Solutions Product Guide 59
MMC Ethernet - TCP/IP Module
60 MMC Controls, Block I/O and Cimrex HMI Motion Solutions Product Guide Sheffield Automation
MMC DeviceNet Module
MMC DeviceNet Module
IntroductionThe MMC DeviceNet scanner module is an interface between the MMC and a DeviceNet network. The module contains an on-board processor, a DeviceNet compliant interface, and firmware that makes it act as the master to all other nodes on the network.
Prior to initial operation, a file is generated with specific configuration software in an external PC. This file must be downloaded via the RS232 configuration port to the DeviceNet module prior to initial operation. Two indicator LEDs (IN/OUT) are connected to this configuration port.
Directly above the DeviceNet port are two LEDs that provide operation information: Network Status and DeviceNet Scanner Status.
The DIAG LED goes on briefly while the diagnostic tests are running.
MMC DeviceNet Module
Diagnostic LED
CNFG
NETWORK
DeviceNetTM
DIAG
PORT
IN OUTCNFG PORT
STATUSSCANNERSTATUS
Configuration Port LEDs
Network/Scanner LEDs
DeviceNettm
PORT
DeviceNet Port
Configuration Port
Sheffield Automation MMC Controls, Block I/O and Cimrex HMI Motion Solutions Product Guide 61
MMC DeviceNet Module
Connections DeviceNet connections are illustrated in Figure B1-. Up to 63 DeviceNet Nodes may be attached to the DeviceNet scanner module.
DeviceNet Connections
MMC DeviceNetD
evic
eNet
Nod
e
Dev
iceN
et N
ode
Dev
iceN
et N
ode To DeviceNet TrunkTo DeviceNet Trunk
CNFG
NETWORK
DeviceNettm
DIAG
PORT
IN OUTCNFG PORT
STATUSSCANNER
STATUS
DeviceNetTM
PORT
PC connected to RS232 portfor downloading file generatedwith Giddings & Lewis DeviceNetconfiguration software.
62 MMC Controls, Block I/O and Cimrex HMI Motion Solutions Product Guide Sheffield Automation
MMC DeviceNet Module
The DeviceNet PortThe DeviceNet port is on the front of the module near the center as shown in Figure B1-. The pinout for the DeviceNet port is shown below:
In your network layout, follow DeviceNet specifications. Only use DeviceNet compliant cable, such as Belden 3084A thin wire and Belden 3082A thick wire.
The Configuration (RS232) PortThere is an RS232 port on the lower front of the module as shown in Figure B1-. This is used to connect to a PC in order to download a file representing your DeviceNet network.
Pin # Signal Name Standard Wire Colors
1 V- black
2 CAN_L blue
3 Shield (drain) bare
4 CAN_H white
5 V+ red
Pin # Signal Name In/Out
2 Receive Data In
3 Transmit Data Out
5 Ground In/Out
Sheffield Automation MMC Controls, Block I/O and Cimrex HMI Motion Solutions Product Guide 63
MMC DeviceNet Module
LEDsThe two configuration port LEDs and the two DeviceNet port LEDs are described below.
DeviceNet PortLED Color State DefinitionNetwork status None OFF Off-line
Green ON On-line and connected to at least one node
Flashing On-line but connection nodes not established
Red ON Unrecoverable Fault (duplicate MAC ID check failed, critical bus fault etc.)
Flashing I/O connections in timed-out state or other Recoverable Fault
Scannerstatus
Green OFF No power or else reset asserted
ON Scanner OK and active
Flashing Scanner OK but not active
Red ON Hardware or software error
Flashing Recoverable configuration error (invalid data downloaded)
Orange ON Configuration (download) mode
Configuration Port
IN Red Flickering Data is being passed to the module
OFF No data to the module
OUT Red Flickering Data is being passed from the mod-ule
OFF No data from the module
64 MMC Controls, Block I/O and Cimrex HMI Motion Solutions Product Guide Sheffield Automation
MMC DeviceNet Module
Theory of OperationThe DeviceNet scanner module provides a memory image of the nodes (slaves) connected to a DeviceNet network. It is this memory image that is controlled by your LDO created in PiCPro. The module’s on-board processor continually transfers data between this memory image and the actual DeviceNet nodes.
Communication between the DeviceNet module and the nodes can be set at 125 Kbaud, 250 Kbaud, or 500 Kbaud. The baud rate, the relationship between the memory image and specific data in each node, and other parameters are established with configuration software run in an external PC.
This configuration software generates two files. One file is downloaded to the DeviceNet module through its RS232 serial port. The other file is used by PiCPro to establish the relationship between the memory image and the declared variables in the LDO. To ensure that a given location in the memory image is connected to a variable in the LDO and to the corresponding data in the DeviceNet node, the same tag name or label must be used.
For example, when running the configuration software, PROX_SW1 could be used as the name for the boolean bit representing a DeviceNet proximity switch’s logic state. The name PROX_SW1 must also be used for the corresponding variable in your LDO.
NOTE
The G&L DeviceNet configuration software (G&L Part No.M.1300.7217) is required to configure the DeviceNet scanner (withinthe DeviceNet module) for the devices on the associated network.
NOTE
Additional information about DeviceNet can be obtained fromwww.odva.org.
Sheffield Automation MMC Controls, Block I/O and Cimrex HMI Motion Solutions Product Guide 65
MMC DeviceNet Module
Specifications
Characteristics DeviceNet Module Specifications
Function Interfaces to a DeviceNet network with up to 63 other nodes
Part number M.1017.3889 (old # 503-26684-00)
DeviceNet Port Phoenix style 5-pin male connector
Configuration Port RS232 interface
24 V DC Power from the MMC 100 mA
Operating temperature range 7° C to 55° C (45° F to 131° F)
Storage temperature range -40° C to 85° C (-40° F to 185° F)
Humidity 5 to 95%, non-condensing
CE Marked Conforms to Directives 73/23/EEC, 89/336/EEC, 92/31/EEC, 93/68/EEC by conforming to the following standards:EN 50081-2:1993 EMC Generic Industrial EmissionsEN 50082-2:1995 EMC Generic Industrial ImmunityEN 61131-2:1994/A11:1996 Low voltage directive requirements for programmable controllersOperates with emissions below EN55011/ CISPR 11Class A limitsImmune to:• Electrostatic discharge (4K V contact mode, 8K V air discharge) per EN61000-4-2• RF electromagnetic fields per EN61000-4-3, ENV 50141, and ENV50204• Electrical fast transients per EN61000-4-4 • Magnetic fields per EN61000-4-8Refer to the EMC Guidelines for more information.
UL and C/UL Listed File No. E126417 NRAQ Programmable Controllers
Physical size 1.3" wide x 9.6" high x 5.3" deep33 mm x 244 mm x 135 mm
Vibration (per IEC 68-2-6) 10-57 Hz (constant amplitude .15 mm)57 - 2000 Hz (acceleration 2 g)
Shock (per IEC 68-2-27) Four shocks per axis (15g/11 msec)
66 MMC Controls, Block I/O and Cimrex HMI Motion Solutions Product Guide Sheffield Automation
MMC Profibus Module
MMC Profibus Module
Introduction
The MMC Profibus scanner module is an interface between the MMC and a Profibus network. The module contains an on-board processor, a Profibus compliant interface, and firmware that makes it act as the master to all other nodes on the network.
Prior to initial operation, a file is generated with specific configuration software in an external PC. This file must be downloaded via the RS232 configuration port to the Profibus module prior to initial operation. Two indicator LEDs (IN/OUT) are connected to this configuration port.
Directly above the Profibus port are two LEDs that provide operation information: Network Status and Profibus Scanner Status.
The DIAG LED goes on briefly while the diagnostic tests are running.
MMC Profibus Module
Diagnostic LED
CNFG
NETWORK
Profibus
DIAG
PORT
IN OUTCNFG PORT
STATUSSCANNERSTATUS
Configuration Port LEDs
Network/Scanner LEDs
Profibus Port
Configuration Port
ProfibusPORT
Sheffield Automation MMC Controls, Block I/O and Cimrex HMI Motion Solutions Product Guide 67
MMC Profibus Module
Connections
Profibus connections are illustrated below. Up to 31 Profibus nodes, without repeaters, may be attached to the Profibus scanner. Up to 125 other Profibus Nodes, using repeaters, may be attached to the Profibus scanner module.
Profibus Connections
PC connected to RS232 port for downloading file generated
MMC Profibus
with Giddings & Lewis Profibus
Pro
fibus
Nod
e
Pro
fibus
Nod
e
Pro
fibus
Nod
e
To Profibus TrunkTo Profibus Trunk
configuration software
CNFG
NETWORK
Profibus
DIAG
PORT
IN OUTCNFG PORT
STATUSSCANNER
STATUS
ProfibusPORT
68 MMC Controls, Block I/O and Cimrex HMI Motion Solutions Product Guide Sheffield Automation
MMC Profibus Module
The Profibus Port
The Profibus port is on the front and center of the module. The pinout for the Profibus port is shown below:
The Configuration (RS232) Port
There is an RS232 port on the lower front of the module. This is used to connect to a PC in order to download a file representing your Profibus network.
Pin # Signal Name Note:It is strongly recommended that you use Profibus Sub-D connectors with switchable (ON/OFF) ter-mination, such as Siemens6ES7 972-0BA11-0XA0 or6ES7 972-0BB11-0XA0.Only use Profibus type A cable, such as Belden 3079A or Siemens 6XV1 830-0AH10.
1 Chassis ground
2 reserved
3 data +
4 Tx enable
5 Isolated ground
6 voltage plus
7 reserved
8 data -
9 reserved
Pin # Signal Name In/Out
2 Receive Data In
3 Transmit Data Out
5 Ground In/Out
Sheffield Automation MMC Controls, Block I/O and Cimrex HMI Motion Solutions Product Guide 69
MMC Profibus Module
LEDs
The two configuration port LEDs and the two Profibus port LEDs are described below.
Profibus PortLED Color State DefinitionNetwork status Green OFF Off-line
ON On-line and connected to at least one node
Red ON On-line but bus error present (baud rate or wiring problem)
Scannerstatus
Green OFF No power or else reset asserted, interface closed
ON Scanner OK and active (inter-face open)
Red ON Interface open, at least one slave faulted
Orange ON Configuration (download) mode
Configuration Port
IN Red Flickering Data is being passed to the module
OFF No data to the moduleOUT Red Flickering Data is being passed from the
moduleOFF No data from the module
70 MMC Controls, Block I/O and Cimrex HMI Motion Solutions Product Guide Sheffield Automation
MMC Profibus Module
Theory of Operation
The Profibus scanner module provides a memory image of the nodes (slaves) connected to a Profibus network. It is this memory image that is controlled by your LDO created in PiCPro. The module’s on-board processor continually transfers data between this memory image and the actual Profibus nodes.
Communication between the Profibus module and the nodes can be set between 9600 baud (1200m max.) and 12M baud (100m max.). The baud rate, the relationship between the memory image and specific data in each node, and other parameters are established with configuration software run in an external PC.
This configuration software generates two files. One file is downloaded to the Profibus module through its RS232 serial port. The other file is used by PiCPro to establish the relationship between the memory image and the declared variables in the LDO. To ensure that a given location in the memory image is connected to a variable in the LDO and to the corresponding data in the Profibus node, the same tag name or label must be used.
For example, when running the configuration software, PROX_SW1 could be used as the name for a boolean bit of a Profibus Block I/O. It would correspond to the wiring location of a proximity switch. The name PROX_SW1 must also be used for the corresponding variable in your LDO.
NOTE
The G&L Profibus configuration software (G&L Part No.M.1300.7218) is required to configure the Profibus scanner (withinthe Profibus module) for the devices on the associated network.
NOTE
Additional information about Profibus can be obtained at www.profi-bus.com
Sheffield Automation MMC Controls, Block I/O and Cimrex HMI Motion Solutions Product Guide 71
MMC Profibus Module
Specifications
Characteristics Profibus Module Specifications
Function Interfaces (acts as DP Master - Class 1), to a Profibus network with up to 125 other nodes, using repeaters
Part number M.1300.7167
Profibus Port 9-pin female D-sub connector
Configuration Port RS232 interface
24 V DC Power from the MMC 100 mA
Operating temperature range 7° C to 55° C (45° F to 131° F)
Storage temperature range -40° C to 85° C (-40° F to 185° F)
Humidity 5 to 95%, non-condensing
CE Marked Conforms to Directives 73/23/EEC, 89/336/EEC, 92/31/EEC, 93/68/EEC by conforming to the following standards:EN 50081-2:1993 EMC Generic Industrial Emis-sionsEN 50082-2:1995 EMC Generic Industrial Immu-nityEN 61131-2:1994/A11:1996 Low voltage directive requirements for programmable controllersOperates with emissions below EN55011/ CISPR 11Class A limitsImmune to:• Electrostatic discharge (4K V contact mode, 8K V air discharge) per EN61000-4-2• RF electromagnetic fields per EN61000-4-3, ENV 50141, and ENV50204• Electrical fast transients per EN61000-4-4 • Magnetic fields per EN61000-4-8Refer to the EMC Guidelines for more information.
UL and C/UL Listed File No. E126417 NRAQ Programmable Controllers
Physical size 1.3" wide x 9.6" high x 5.3" deep33 mm x 244 mm x 135 mm
Vibration (per IEC 68-2-6) 10-57 Hz (constant amplitude .15 mm)57 - 2000 Hz (acceleration 2 g)
Shock (per IEC 68-2-27) Four shocks per axis (15g/11 msec)
72 MMC Controls, Block I/O and Cimrex HMI Motion Solutions Product Guide Sheffield Automation
MMC CONTROLS, BLOCK I/O AND CIMREX HMIMOTION SOLUTIONS PRODUCT GUIDE
MMC for PC(PC Machine and Motion Control)
Sheffield Automation
MMC for PC (PC Machine and Motion Control)
Description. The MMC for PC (PC Machine and Motion Control) is a full-featured total machine control solution for applications requiring up to 32 axes of analog or SERCOS interfaced servo motion control. The MMC for PC is a half-slot PCI card that can be installed in a Windows NT or Windows 2000 or Windows XP Professional Edition personal computer.
Programming. The MMC for PC is programmed using IEC1131 ladder logic, function blocks, and structured text using the Professional Edition of PiCPro for Windows. Programs developed for PiC and stand-alone MMC are 100% compatible with the MMC for PC. The MMC for PC communicates with PiCPro for Windows via the host PC’s local Ethernet stack.
Features. Using the MMC for PC, you have the power of PiCPro for Windows at your fingertips. A mature and reliable product, PiCPro for Windows offers animation, variable force and view, cam profiles, linear and circular interpolation, registration, multi-tasking, and UDFBs as standard features. With virtually no re-programming, an application can be loaded into an MMC, PiC or MMC for PC control. This allows you to expand your motion control system from one product to another without wasting valuable engineering time. The MMC for PC status software makes it easy to maintain and troubleshoot your application.
Expanded Features. The MMC for PC hardware allows you to wire an external 24V power supply to the PCI card. In the event power is shut down from the host PC, the MMC for PC will automatically switch over to using this power supply, allowing uninterrupted
Up to 32Axes
MMC for PC - SERCOS System
MMC for PC - Analog System
Up to 32Axes
Up to 8ASIUs
SERCOS Ring(fiber optic)
Block I/OUp to 32 Axes
MMC for PC
MMC for PC
Amplifiers Block I/OASIU(Analog Servo
PCI Bus
PCI Bus
Interface Unit)
Up to 32Axes
Motion Network(CAT5 Cable)
74 MMC Controls, Block I/O and Cimrex HMI Motion Solutions Product Guide Sheffield Automation
control of the machine. The IPSTAT function in PiCPro for Windows indicates to the application program that communication with Windows NT has been lost so appropriate action can be taken.
HMI. Use the PC for your HMI as well as to house the MMC for PC control. Name based data transfer using the Giddings & Lewis OPC Server allows the MMC for PC to communicate with any OPC client on the host PC. Giddings & Lewis CEZAR software is a full-featured, easy-to-use PC HMI software package.
Hardware Connections. The hardware connections made to the MMC for PC PCI processor card are robust and clean. For SERCOS MMC for PC systems, the PCI card is connected to the ring of servo amplifiers with fiber optic cable. For analog MMC for PC systems, the PCI card is connected to up to eight ASIU (analog servo interface units) with CAT-5 Ethernet cable. The connections to servo amplifiers and real time I/O are made to the ASIU and transferred over a high-speed proprietary serial link to the MMC for PC processor board.
I/O. Use the Giddings & Lewis Block I/O, DeviceNet or Profibus. Giddings & Lewis Block I/O is standard on the MMC for PC. A complete family of Block I/O Modules are available, including AC and DC discrete I/O, analog input and output, and stepper output. The MMC for PC processor communicates to Block I/O Modules over a high speed proprietary twisted pair cable. Up to 77 Block I/O Modules can be connected to the processor board. DeviceNet and Profibus are field installable option cards that plug on to the MMC for PC processor board. Both are master scanner cards that communicate with the MMC for PC using shared memory.
MMC for PC SERCOS
Connection to... How Details
Machine I/O 4-wire screw terminal Up to 77 Giddings & Lewis Block I/O Modules
SERCOS Amplifiers Fiber-optic Connect up to 32 SERCOS amplifiers in a ring configuration
Real-time I/O Fiber-opticWire real-time I/O to the SERCOS amplifiers and read/write the information over the SERCOS ring
External Power Supply (optional) Screw terminalAllows you to continue to control the machine in the event of a PC power cycle
DeviceNet network N/AConnection made on DeviceNet daughter card - width of 2 PCI slots required
Profibus network N/A Connection made on Profibus daughter card - width of 2 PCI slots required
Digital Line Shaft Cat-5 Ethernet Cable Connection made on DLS daughter card - width of 2 PCI slots required
Sheffield Automation MMC Controls, Block I/O and Cimrex HMI Motion Solutions Product Guide 75
ASIU Connections:
Axis A1 to A4 Connectors. On the ASIU, each axis connector (labeled A1 to A4) provides a connection to a servo amplifier. Each axis connector contains a differential encoder input, a +/- 10V analog output, two 24VDC discrete outputs for drive enable and drive reset, and one 24VDC discrete input for the drive ready or drive OK signal. Only one cable is required to interface an ASIU to a Centurion DSA or MicroDSA amplifier. Encoder inputs and analog outputs not used for closed loop servos can be used for variable frequency drives or additional master axes.
Aux I/O. On the ASIU, the Aux I/O connector contains the fast inputs for each axis (including the half axis encoder input) for registration and hardware interrupt capability. It also contains the differential encoder input for the half axis, one analog input, and three 24VDC discrete inputs for each closed loop axis. Typically these inputs would be used for plus and minus end of travel limits and for the reference switch. However, they can be used as general purpose inputs if they are not being used for end-of-travel and reference switch.
MMC for PC Analog
Connection to... How Details
Machine I/O 4-wire screw terminal Up to 77 Giddings & Lewis Block I/O Modules
ASIU (Analog Servo Interface Unit) CAT-5 Ethernet Cable
Daisy-chain up to 8 ASIU modules to the MMC for PC Analog processor PCI card
+/- 10V AmplifiersPlug & Play Cables Breakout BoxesFlying Lead Cables
Connection to the amplifiers is made to the ASIU (Analog Servo Interface Unit)
Real-time I/OPlug & Play CablesBreakout BoxesFlying Lead Cables
Connection to the real-time I/O is made to the ASIU (Analog Servo Interface Unit)
External Power Supply (optional) Screw terminalAllows you to continue to control the machine in the event of a PC power cycle
DeviceNet network N/AConnection made on DeviceNet daughter card - width of 2 PCI slots required
Profibus network N/A Connection made on Profibus daughter card - width of 2 PCI slots required
76 MMC Controls, Block I/O and Cimrex HMI Motion Solutions Product Guide Sheffield Automation
Gen I/O. The Gen I/O connector contains sixteen general-purpose 24 VDC discrete inputs (sink or source) and sixteen general-purpose 24 VDC discrete outputs (source only). Any of the 16 outputs can be used as CAM or PLS outputs. Two of the inputs (number 1 and number 9) have hardware interrupt capability and can be used to trigger hardware interrupt tasks in the application program.
Cables. There are a number of plug and play cables available to facilitate ASIU wiring. Four types of cables can be used with the A1 to A4 connectors on the ASIU, including a Centurion MicroDSA drive J1 connector, a Centurion DSA drive J1 connector, a flying lead connector or a breakout box connector. For the AUX I/O and GEN I/O connectors, there are two types of cables that can be used: a breakout box connector or a flying lead connector.
MMC for PC
MMC for PC Part Numbers
Note: The MMC for PC packages include the MMC for PC processor board, theGiddings & Lewis OPC Server, the MMC for PC Software Suite and PiCPro forWindows-Monitor Edition.
MMC for PC Package
Description Part Number
MMC for PC Analog Package M.1301.3089
ASIU-2 M.1300.5970
ASIU-4 M.1300.4422
MMC for PC-S8 SERCOS Package M.1301.4102
MMC for PC-S16 SERCOS Package M.1301.4103
MMC for PC-S32 SERCOS Package M.1301.4104
MMC for PC Hardware Manual M.1300.7621
Sheffield Automation MMC Controls, Block I/O and Cimrex HMI Motion Solutions Product Guide 77
MMC for PC SERCOS Board
The major components of the SERCOS board are illustrated below and include a standard half size 32 bit 5 volt 33Mhz PCI card, a 32-bit RISC processor running at 128 Mhz (with numeric coprocessor), one SERCOS port that includes a fiber optic input connection and output connection for one SERCOS ring, a +24V Power connector, a 9-Pin Block I/O interface port and lithium coin cell backup battery.
+24V PowerConnectorand LockoutSwitch Input
Block I/OInterface Port(to Block I/O)
SERCOSReceivePort (RX)
Component View of MMC for PC SERCOS Board
9 Pin D-subconnector
SERCOSTransmitPort (TX)
End Bracket Face Plate
78 MMC Controls, Block I/O and Cimrex HMI Motion Solutions Product Guide Sheffield Automation
MMC for PC Analog Servo Board
The major components of the Analog Servo board are illustrated below and include a standard half size 32 bit 5 volt 33Mhz PCI card, an 32-bit RISC processor running at 128 Mhz (includes numeric coprocessor), a RJ45 connector for communication with ASIUs, a 9-Pin Block I/O interface port and a a lithium coin cell backup battery
Analog Servo Interface Unit (ASIU)
The Analog Servo Interface Unit (ASIU) provides servo axis interface signals and general purpose I/O for the MMC for PC Analog Board. The ASIU is available in two models, an ASIU-A2 (2 1/2 servo axis unit) and an ASIU-A4 (4 1/2 servo axis unit).
32-bit RISC
+24V PowerConnector
Processor
and LockoutSwitch Input
Block I/OInterface Port(to Block I/O)
PCI Connector
+
Battery
Component View of MMC for PC Analog Servo Board
9 Pin D-subconnector
End Bracket Face Plate
DIAGTO
ASIU
-R+R-V+V
BLOCKI/O
RJ45
(to ASIU)Connector
Sheffield Automation MMC Controls, Block I/O and Cimrex HMI Motion Solutions Product Guide 79
Communication between the ASIU and the MMC for PC Analog Board (mounted in a Personal Computer) is accomplished through the use of a 10Base-T Ethernet interface. The MMC for PC Analog Board can communicate with up to eight ASIUs by connecting the ASIUs together.
Analog Servo Interface Unit (ASIU)
80 MMC Controls, Block I/O and Cimrex HMI Motion Solutions Product Guide Sheffield Automation
ASIU Major Components
Major external components of the ASIU include:
• Two RJ45 connectors and associated communications circuitry to communicate with the MMC for PC Analog Board and other ASIUs.
• A screwdriver-actuated rotary switch (0 through 9) that allows the user to define the ASIU address. Addresses 1 through 8 define valid ASIUs, and addresses 0 and 9 effectively remove the ASIU from the system (the two RJ45 connectors are still active, but the ASIU will not be seen by the MMC for PC Analog Board).
• A 3-pin power connector to supply 24VDC to the ASIU• A General I/O port connector for connecting 16 inputs and 16 outputs to user
devices.• An Auxiliary I/O Port for connecting one quadrature incremental encoder, five
fast DC inputs, one analog input channel and twelve DC inputs to user devices.• Four Axis connectors are available on the ASIU-A4 and two are available on
the ASIU-A2. Axis connections include one analog output, one encoder input, two DC outputs and one DC input to user devices.
• LED indicators include the following:• Scanning (Green) – Indicates CPU is communicating with the ASIU.• Power (Green) – Indicates +5V is OK.• Diagnostic (Yellow) – On briefly during startup. If it remains ON, ASIU
has failed startup diagnostics.• Link OK (Green) – Located near each of two RJ45 connectors. These
LEDs indicate that the attached RJ45 cable is wired correctly and both ends are powered up.
• Collision (Red) – Located in the cut-out area of the plastic faceplate. Indicates that 2 or more ASIUs are at the same address.
• Transmit (Green) – Located in the cut-out area of the plastic faceplate. Indicates that this ASIU is sending a packet of information.
• Receive (Green) – Located in the cut-out area of the plastic faceplate. Indicates that this ASIU is receiving a packet of information.
Sheffield Automation MMC Controls, Block I/O and Cimrex HMI Motion Solutions Product Guide 81
ASIU Axis I/O Points
The ASIU provides conventional analog/digital interfacing for two or four drives.
Typical signals needed to interface to an analog drive are provided by the ASIU. The drive command is in the form of an analog voltage (±10V). Feedback is accepted from quadrature type encoders with RS422 style differential outputs. Digital I/O (+24 VDC) is used for drive enable, reset, and fault signals.
The ASIU is offered in both 2 1/2 (ASIU-A2) and 4 1/2 (ASIU-A4) axis configurations. An axis is considered to be an analog output with a corresponding encoder input. In each configuration shown below, note that there is an extra encoder input. This is referred to as a half axis.
The following table shows the number of I/O points available on the ASIU for the analog MMC for PC.
Available Axis I/O for ASIU
* With the SERCOS MMC for PC, analog inputs, axis inputs, and feedbacksignals are transferred over the SERCOS fiber optic link.
Available I/O* ASIU-2 ASIU-4Analog Inputs 1 1Analog Outputs 2 4Encoder Inputs 3 5Axis DC Inputs 2 4Axis DC Outputs 4 8Axis Fast DC Inputs 3 5AUX I/O Port DC Inputs 6 12General I/O Port DC Inputs 16 16General I/O Port DC Outputs 16 16
82 MMC Controls, Block I/O and Cimrex HMI Motion Solutions Product Guide Sheffield Automation
ASIU Accesories
Connection Selector Sheet for ASIU (Analog Servo Interface Unit)
ASIU-4 4 Axis ASIU shown(ASIU-2 2 Axis ASIU also available)
ACCESSORIES
ACCESSORIES
Sheffield Automation MMC Controls, Block I/O and Cimrex HMI Motion Solutions Product Guide 83
ASIU - Part Numbers
ASIU Connector Cables and Breakout Boxes - Part Numbers
MMC for PC ASIU (Analog Servo Interface Unit)
Description Part NumberASIU-2 2 Axis M.1300.5970ASIU-4 4 Axis M.1300.4422
ASIU Axis Connector Cables and Breakout Box(only for ASIU Servo Control Axis Ports A1, A2, A3, A4)
DSA DriveDescription Length Part Number
MMC Axis A ‘n’ to DSA J1 Connector0.5 Meters M.1301.5537
1 Meter M.1301.55661.5 Meters M.1301.55693 Meters M.1301.5592
Flying LeadDescription Length Part NumberMMC Axis A’n’ to Flying Lead Cable 10’ M.1016.2519 Breakout BoxDescription Length Part Number
MMC Axis A’n’ to Breakout Box Cable1’ M.1016.2535 2’ M.1016.2536 3’ M.1016.2537
MMC Connector Breakout Box N/A M.1016.2529
ASIU Auxiliary I/O Connector Cables and Breakout Box
Flying LeadDescription Length Part NumberMMC Aux I/O Connector to Flying Lead 10’ M.1016.2566 Breakout BoxDescription Length Part Number
MMC Gen/Aux I/O Connector to Breakout Box Cable1’ M.1016.2539 2’ M.1016.2540 3’ M.1016.2541
MMC Aux I/O Breakout Box N/A M.1016.2531 MMC Connector Breakout Box with Encoder Isolation N/A M.1016.4236
ASIU General I/O Connector Cables and Breakout Box
Flying LeadDescription Length Part NumberMMC Gen I/O Connector to Flying Lead 10’ M.1016.2567
Breakout BoxDescription Length Part Number
MMC Gen/Aux I/O Connector to Breakout Box Cable1’ M.1016.2539 2’ M.1016.2540 3’ M.1016.2541
MMC Gen I/O Breakout Box N/A M.1016.2532
84 MMC Controls, Block I/O and Cimrex HMI Motion Solutions Product Guide Sheffield Automation
Breakout Box for Connecting to ASIU
There are three Breakout Boxes available that simplify wire termination to the ASIU. There are two 44-pin type and one15-pin type. The Breakout Box dimensions are shown in the following illustrations.
Dimensions - 44-Pin Breakout Box for AUX I/O and GEN I/O ASIU Connectors
Dimensions - 15-Pin Breakout Box for Axis Port ASIU Connectors
1.875”
2.625”
3.940”
1 22
23 44
1.750”
2.250”
3.000”
1
9
2.250”
8
15
Sheffield Automation MMC Controls, Block I/O and Cimrex HMI Motion Solutions Product Guide 85
ASIU Mounting Dimensions
The ASIU is mounted to your cabinet using the mounting slots on the ASIU. The ASIU may be mounted vertically or horizontally. The recommended size of mounting hardware is #10 bolts with #10 star washers (to ensure proper ground connection).
ASIU Mounting Dimensions
ASIU
.218" (5.54 mm)1.06" (26.9 mm)
Side Cover
Screw Head
.040" Thickness
.080" Thickness
NOTE: Add the sidecover and screw headthicknesses to theunit’s dimensions fortotal width.
86 MMC Controls, Block I/O and Cimrex HMI Motion Solutions Product Guide Sheffield Automation
Optional Fieldbus Modules
The MMC for PC will accept a Fieldbus Module for network communications, either DeviceNet, Profibus, or Digital Line Shaft (DLS). The board is mounted 0.8" above the MMC for PC board. When the Fieldbus Module is mounted on the MMC for PC board, the combined unit will occupy two slots. The board is located so the network connector will be positioned in a slot apeture of the host PC.
Optional Fieldbus Modules - Part Numbers
NOTE
Throughout this document, "Fieldbus Module" is a generic term that refers toany communication module (DeviceNet, Profibus, or Digital Line Shaft (DLS))that can be installed on the MMC for PC board. It does not refer to a specifictype of communication network or module.
Description Part NumberDeviceNet Module M.1300.5981DeviceNet Configuration Software M.1300.7217Profibus Module M.1300.5984Profibus Configuration Software M.1300.7218Digital Line Shaft (DLS) Module M.1301.8981
Fieldbus Module
MMC for PCBoard
View fromComponent Side
Sheffield Automation MMC Controls, Block I/O and Cimrex HMI Motion Solutions Product Guide 87
DeviceNet Module
DeviceNet Connections
PC containing MMC for PC BoardD
evic
eNet
Nod
e
Dev
iceN
et N
ode
Dev
iceN
et N
ode To DeviceNet TrunkTo DeviceNet Trunk
with attached Fieldbus Module
NET
SCN
DEVICENET
PORT
ScannerStatus LED
NetworkStatus LED
Phoenix 5-pin Connector
DeviceNet Port
DeviceNet Network Configuration
Pinout for DeviceNet Port
Pin # Signal Name
1
2
3
4
5
V-
CAN_L
Shield (drain)
CAN_H
V+
Wiire Color
black
blue
bare
white
red
1
5
88 MMC Controls, Block I/O and Cimrex HMI Motion Solutions Product Guide Sheffield Automation
DeviceNet Module LEDs
LED Color State DefinitionNetwork Status Green OFF Off-line
ON On-line and connected to all nodesFlashing On-line but connection to all nodes
not establishedRed ON Unrecoverable Fault (duplicate
MAC ID check failed, critical bus fault, etc.)
Flashing I/O connections in timed-out state or other Recoverable Fault
Scanner Status Green OFF No power or else reset assertedON Scanner OK and activeFlashing Scanner OK but not active
Red ON Hardware or software errorFlashing Recoverable configuration error
(invalid data downloaded)Orange ON Configuration (download) mode
Sheffield Automation MMC Controls, Block I/O and Cimrex HMI Motion Solutions Product Guide 89
Profibus Module
Profibus Connections
PC containing MMC for PC BoardP
rofib
us N
ode
Pro
fibus
Nod
e
Pro
fibus
Nod
e
To Profibus segmentTo Profibus segment
with attached Fieldbus Module
Profibus Network Configuration
NET
SCN
PROFIBUS
PORT
ScannerStatus LED
NetworkStatus LED
9 Pin D-sub Connector
Profibus Port
Pinout for Profibus Port
Pin # Signal Name
1
2
3
4
5
6
7
8
9
Chassis ground
Reserved
data +
Tx enable
Isolated ground
voltage +
reserved
data -
reserved
1
95
6
90 MMC Controls, Block I/O and Cimrex HMI Motion Solutions Product Guide Sheffield Automation
Profibus Module LEDs
LED Color State DefinitionNetwork Status Green OFF Off-line
ON On-line and connected to all nodesRed ON On-line, but bus error (baud rate or
wiring problem)Scanner Status Green OFF No power or else reset asserted,
interface closedON Scanner OK and active (interface
open)Red ON Interface open, at least one slave
faultedOrange ON Configuration (download) mode
Sheffield Automation MMC Controls, Block I/O and Cimrex HMI Motion Solutions Product Guide 91
Digital Line Shaft (DLS) ModuleUp to 256 SERCOS axes can be synchronized using the Digital Line Shaft (DLS) fieldbus module. The DLS master provides real-time communication of either actual or commanded postion of the system master axis (time or real servo axis) as well as registration offset and E-Stop status to all Digital Line Shaft slaves.
DLS Connections
PC containing MMC for PC Board
DLS
Mod
ule
DLS
Mod
ule
DLS
Mod
ule
DLS
Mod
ule
DLS
Mod
ule
DLS
Mod
ule
DLS
Mod
ule
In Out In Out In Out In Out In Out In Out In Out
Category 5 Cable (Maximum Length = 25 meters)
DLS
PORTS
IN
OUT
with attached DLS module.
Up to 8 MMC for PCs with Digital Line Shaft Modules can be connectedas shown above. Each module resides on an MMC for PC SERCOS board.
The DLS ports use RJ-45 style 8-pin connectors using 100 ohmunshielded twisted pair category 3 or 5 cable (IEEE 802.3 Section 14.4).
NOTE: The connector is also suitable for shielded cable and will groundthe shield to the chassis.
NOTE: The DLS Module can only be used the MMC for PC-S8(P/N M.1301.4102), MMC for PC-S16 (P/N M.1301.4103),
The maximum length of the twisted pair cable segment is 25m (82.5 ft.).
or MMC for PC-S32 (P/N 1301.4104).
92 MMC Controls, Block I/O and Cimrex HMI Motion Solutions Product Guide Sheffield Automation
DLS Module LEDs
In Link OK(IN OK) Green
ON Indicates that there is a DLS Module properly connected and communicating with this DLS Module’s IN port.
OFF Indicates that there is not a DLS Module properly connected and communicating with this DLS Module’s IN port.
Out Link OK(OUT OK) Green
ON Indicates that there is a DLS Module properly connected and communicating with this DLS Module’s OUT port.
OFF Indicates that there is not a DLS Module properly connected and communicating with this DLS Module’s OUT port.
Sheffield Automation MMC Controls, Block I/O and Cimrex HMI Motion Solutions Product Guide 93
Specification Tables
MMC for PC Analog Board Specifications
*Where two numbers are listed they represent High/Low. The High number is typical when running RATIO_GR, RATIOCAM, VEL_STRT, POSITION, DISTANCE move types etc... The Low number is typical when running time axes, servo tasks, RATIO_RL, M_LINCIR, M_SCRVLC move types etc... The Low number types place a heavier burden on CPU time than the High number types.
Servo Update Rates
Update Rates
8 ms 4 ms 2 ms 1 ms .5 ms .25 ms
Maximum number of axes* 32 32 32 24/12 12/6 6/3
Maximum number of ASIUs 8 8 8 6 3 2
General
Part Number Use MMC for PC Analog Package M.1301.3089
System Requirements One PCI Local Bus slot, Standard 2.1 compatible, 133MHz Pentium or faster
Processor Speed 128MHz
Board Dimensions 6.6" L x 4.2" H
Flash Memory 1 MB
RAM Memory 1MB (Refer to the PiCPro for Windows Software Manual for partitioning, RAM into Application, RAM Disk and Variable Memory storage areas)
Input voltage range +20 VDC to 30 VDC (absolute maximum),24V nominal
Input power 6.5 W @ 24V (.27 amps), PCI bus derived or external
Environmental
Operating temperature range 0°C to 55°C (32° F to 131°F)
Storage temperature range -40°C to 85°C (-40°F to 185°F)
Humidity 5 to 95%, non-condensing
94 MMC Controls, Block I/O and Cimrex HMI Motion Solutions Product Guide Sheffield Automation
Conformity
CE Marked Conforms to Directives 73/23/EEC, 89/336/EEC, 92/31/EEC, 93/68/EEC by conforming to the following standards:EN 50081-2:1993EMC Generic Industrial EmissionsEN 50082-2:1995EMC Generic Industrial ImmunityEN 61131-2:1994/A11:1996 Low voltage directive requirements for programmable controllersOperates with emissions below EN55011/ CISPR 11Class A limitsImmune to:• Electrostatic discharge (4K V contact mode, 8K V air discharge) per EN61000-4-2• RF electromagnetic fields per EN61000-4-3, ENV 50141, and ENV50204• Electrical fast transients per EN61000-4-4 • Magnetic fields per EN61000-4-8Refer to the EMC Guidelines for more information.
UL and C/UL Listed File No. E126417 NRAQ Programmable Controllers
Sheffield Automation MMC Controls, Block I/O and Cimrex HMI Motion Solutions Product Guide 95
MMC for PC SERCOS Board Specifications
Servo Update Rates
Update Rates
8 ms 4 ms 2 ms 1 ms
Maximum number of axes 32 32 16 8
General
Part Number MMC for PC-S8 (8 axes) M.1301.4102MMC for PC-S16 (16 axes) M.1301.4103MMC for PC-S32 (32 axes) M.1301.4104
System Requirements One PCI Local Bus slot, Standard 2.1 and 2.2 compatible 133MHz Pentium or faster
Processor Speed 128Mhz
Board Dimensions 6.6" L x 4.2" H
Flash Memory 1 MB
RAM Memory 1MB (Refer to the PiCPro for Windows Software Manual for partioning RAM into Application, RAM Disk and Variable Memory storage areas)
Input voltage range +20 VDC to 30V DC (absolute maximum),24V nominal
Input power 6.5 W @ 24V (.27 amps), PCI bus derived or external
Environmental
Operating temperature range 0°C to 55°C (32° F to 131°F)
Storage temperature range -40°C to 85°C (-40°F to 185°F)
Humidity 5 to 95%, non-condensing
96 MMC Controls, Block I/O and Cimrex HMI Motion Solutions Product Guide Sheffield Automation
ASIU Specifications
Conformity
CE Marked Conforms to Directives 73/23/EEC, 89/336/EEC, 92/31/EEC, 93/68/EEC by conforming to the following standards:EN 50081-2:1993EMC Generic Industrial EmissionsEN 50082-2:1995EMC Generic Industrial ImmunityEN 61131-2:1994/A11:1996 Low voltage directive requirements for programmable controllersOperates with emissions below EN55011/ CISPR 11Class A limitsImmune to:• Electrostatic discharge (4K V contact mode, 8K V air discharge) per EN61000-4-2• RF electromagnetic fields per EN61000-4-3, ENV 50141, and ENV50204• Electrical fast transients per EN61000-4-4 • Magnetic fields per EN61000-4-8Refer to the EMC Guidelines for more information.
UL and C/UL Listed File No. E126417 NRAQ Programmable Controllers
General
Part Number for ASIU-2 M.1300.5970
Part Number for ASIU-4 M.1300.4422
IN and OUT RJ45 ports RJ45 port, secured protocol
Input voltage range +20 VDC to 30 VDC (absolute maximum),24V nominal
Input power 350 mA plus I/O power
Operating temperature range 5°C to 55°C (41°F to 131°F)
Storage temperature range -40°C to 85°C (-40°F to 185°F)
Humidity 5 to 95%, non-condensing
Maximum length of cable between MMC for PC Analog board and first ASIU
82.5 ft.(25 m)
Maximum length of cable between two ASIUs
82.5 ft.(25 m)
Type of cable between MMC for PC Analog board and first ASIU
CAT5 straight pinned. Use shielded cable in noisy environments.
Type of cable between two ASIUs CAT5 straight pinned. Use shielded cable in noisy environments.
Sheffield Automation MMC Controls, Block I/O and Cimrex HMI Motion Solutions Product Guide 97
MMC for PC DeviceNet Module Specifications
General
Part Number M.1300.5981
Function Interfaces to a DeviceNet network with up to 63 other nodes.
DeviceNet Port Phoenix style 5-pin male connector
Supply Voltage Range 4.75 V to 5.25 V
Supply Current (steady state) 500 mA maximum (250 mA typical)
Peak Supply Current 750 mA
Vibration (per IEC 68-2-6) 10-57 Hz (constant amplitude .15 mm)57 - 2000 Hz (acceleration 2 g)
Shock (per IEC 68-2-27) Four shocks per axis (15g/11 msec)
Environmental
Operating Ambient Temperature 0°C to 60°C (32° F to 140°F)
Non-operating Ambient Temperature -25°C to 70°C (-13° F to 158°F)
Operating Humidity 5 to 95% non-condensing
Conformity
CE Marked Conforms to Directives 73/23/EEC, 89/336/EEC, 92/31/EEC, 93/68/EEC by conforming to the following standards:EN 50081-2:1993EMC Generic Industrial EmissionsEN 50082-2:1995EMC Generic Industrial ImmunityEN 61131-2:1994/A11:1996 Low voltage directive requirements for programmable controllersOperates with emissions below EN55011/ CISPR 11Class A limitsImmune to:• Electrostatic discharge (4K V contact mode, 8K V air discharge) per EN61000-4-2 RF electromagnetic fields per EN61000-4-3, ENV 50141, and ENV50204• Electrical fast transients per EN61000-4-4 • Magnetic fields per EN61000-4-8. Refer to the EMC Guidelines for more information.
File No. E126417 NRAQ Programmable Controllers
98 MMC Controls, Block I/O and Cimrex HMI Motion Solutions Product Guide Sheffield Automation
MMC for PC Profibus Module Specifications
General
Part Number M.1300.5984
Function Interfaces to a Profibus network with up to 31 other nodes, without a repeater.
Profibus Port 9-pin D-sub female connector
Supply Voltage Range 4.75 V to 5.25 V
Supply Current (steady state) 500 mA maximum (250mA typical)
Peak Supply Current 750 mA
Vibration (per IEC 68-2-6) 10-57 Hz (constant amplitude .15 mm)57 - 2000 Hz (acceleration 2 g)
Shock (per IEC 68-2-27) Four shocks per axis (15g/11 msec)
Environmental
Operating Ambient Temperature 0°C to 60°C (32° F to 140°F)
Non-operating Ambient Temperature -25°C to 70°C (-13° F to 158°F)
Operating Humidity 5 to 95% non-condensing
Conformity
CE Marked Conforms to Directives 73/23/EEC, 89/336/EEC, 92/31/EEC, 93/68/EEC by conforming to the following standards:EN 50081-2:1993EMC Generic Industrial EmissionsEN 50082-2:1995EMC Generic Industrial ImmunityEN 61131-2:1994/A11:1996 Low voltage directive requirements for programmable controllersOperates with emissions below EN55011/ CISPR 11Class A limitsImmune to:• Electrostatic discharge (4K V contact mode, 8K V air discharge) per EN61000-4-2• RF electromagnetic fields per EN61000-4-3, ENV 50141, and ENV50204• Electrical fast transients per EN61000-4-4 • Magnetic fields per EN61000-4-8Refer to the EMC Guidelines for more information.
UL and C/UL Listed File No. E126417 NRAQ Programmable Controllers
Sheffield Automation MMC Controls, Block I/O and Cimrex HMI Motion Solutions Product Guide 99
MMC for PC Digital Line Shaft (DLS) Module Specifications
General
Part Number M.1301.8981
Function Interfaces up to 8 Digital Line Shaft Modules as part of a cluster of up to 8 MMC for PC systems.
DLS Ports Two RJ45 Shielded Connectors, one for Input,one for Output.
Supply Voltage Range 4.75 V to 5.25 V
Supply Current (steady state) 500 mA maximum (250mA typical)
Peak Supply Current 750 mA
Vibration (per IEC 68-2-6) 10-57 Hz (constant amplitude .15 mm)57 - 2000 Hz (acceleration 2 g)
Shock (per IEC 68-2-27) Four shocks per axis (15g/11 msec)
Environmental
Operating Ambient Temperature 0° C to 55° C (32° F to 131° F)
Non-operating Ambient Temperature -25° C to 70° C (-13° F to 158° F)
Operating Humidity 5 to 95% non-condensing
Conformity
CE Marked(Pending)
Conforms to Directives 73/23/EEC, 89/336/EEC, 92/31/EEC, 93/68/EEC by conforming to the following standards:EN 50081-2:1993EMC Generic Industrial EmissionsEN 50082-2:1995EMC Generic Industrial ImmunityEN 61131-2:1994/A11:1996 Low voltage directive requirements for programmable controllersOperates with emissions below EN55011/ CISPR 11Class A limitsImmune to:• Electrostatic discharge (4K V contact mode, 8K V air discharge) per EN61000-4-2• RF electromagnetic fields per EN61000-4-3, ENV 50141, and ENV50204• Electrical fast transients per EN61000-4-4 • Magnetic fields per EN61000-4-8Refer to the EMC Guidelines for more information.
UL and C/UL Listed File No. E126417 NRAQ Programmable Controllers
100 MMC Controls, Block I/O and Cimrex HMI Motion Solutions Product Guide Sheffield Automation